These are my notes on configuring lm_sensors on the SuperMicro P3TDDR motherboard. This dual PIII motherboard is found in the SuperMicro 6011H server.
In case you don't know what this page is for, lm_sensors is the linux software package for reading the sensor data (temperatures, fan speeds, voltages) that is available on many modern motherboards.
dmidecode output:
Manufacturer: Supermicro Product Name: P3TDDR
I found the correct modules to run by running /usr/sbin/sensors-detect. Modules:
i2c-viapro i2c-isa eeprom w83781d
Note that sensors-detect tells you to load the w83627hf module, which I think may exist in newer versions of lm_sensors. I didn't have that so I tried the w83781d module instead. Appears to work fine.
Here's the /etc/sensors.conf:
chip "w83782d-*" "w83627hf-*"
label in0 "VCore 1"
label in1 "VCore 2"
label in2 "+3.3V"
label in3 "+5V"
label in4 "+12V"
label in5 "-12V"
label in6 "-5V"
label in7 "V5SB"
label in8 "VBat"
compute in3 ((6.8/10)+1)*@ , @/((6.8/10)+1)
compute in4 ((28/10)+1)*@ , @/((28/10)+1)
compute in5 (5.14 * @) - 14.91 , (@ + 14.91) / 5.14
compute in6 (3.14 * @) - 7.71 , (@ + 7.71) / 3.14
compute in7 ((6.8/10)+1)*@ , @/((6.8/10)+1)
# set limits to 5% for the critical voltages
# set limits to 10% for the non-critical voltages
# set limits to 20% for the battery voltage
set in0_min vid*0.95
set in0_max vid*1.05
set in1_min vid*0.95
set in1_max vid*1.05
set in2_min 3.3 * 0.95
set in2_max 3.3 * 1.05
set in3_min 5.0 * 0.95
set in3_max 5.0 * 1.05
set in4_min 12 * 0.90
set in4_max 12 * 1.10
set in5_max -12 * 0.90
set in5_min -12 * 1.10 set in7_min 5 * 0.95
set in7_max 5 * 1.05
set in8_min 3.0 * 0.80
set in8_max 3.0 * 1.20
label fan1 "CPU1 Fan"
label fan2 "CPU2 Fan"
label fan3 "Chs1 Fan"
# These systems use one big fan for all cpus.
ignore fan1
ignore fan2
label temp1 "Chs1 Temp"
label temp2 "CPU2 Temp"
label temp3 "CPU1 Temp"
set in6_max -5 * 0.95
set in6_min -5 * 1.05
You should ignore the CPU2 temperature if you oinly have one cpu installed.
/usr/bin/sensors output should look something like this: